U3GK0911-XX Online UPS 1–3 kVA

The U3GK0911-XX is an online double-conversion UPS (1–3 kVA (1:1)) with 0.9 output power factor, built on advanced DSP technology. It gives connected loads a clean, uninterrupted supply with zero transfer time.

Description

The U3GK0911-XX is an online double-conversion UPS (1–3 kVA (1:1)) with 0.9 output power factor, built on advanced DSP technology. It gives connected loads a clean, uninterrupted supply with zero transfer time.

Wide input voltage range, parallel operation and flexible battery configuration make it suitable for offices, data rooms and industrial loads.

  • Advanced DSP (digital signal processor) control
  • Wide input voltage range; 50/60 Hz auto-sensing
  • Linear derating at low input voltage, reducing battery discharge and extending battery life
  • Dual-input design with independent bypass
  • Flexible battery configuration (16–20 batteries); charging voltage and current set on demand
  • Cold start from battery; settable delayed restart when mains returns
  • Frequency conversion: 50 Hz in / 60 Hz out or 60 Hz in / 50 Hz out
  • LCD + LED display with multi-function keys
  • Configuration software for all parameters
  • Communication: RS232, USB, RS485, SNMP and dry contacts
  • Intelligent battery management (float / equalizing charge, charger dormancy), up to 50% longer battery life
  • Active power factor correction, input power factor up to 0.99
  • High efficiency: 95% (up to 98% in ECO mode)
  • Variable-speed fans, self-diagnostics, event log and self-aging function

Technical Parameters

Model U3GK091106 U3GK091110 U4GK091115
Capacity 1 kVA / 900 W 2 kVA / 1800 W 3 kVA / 2700 W
Built-in Battery (standard model) 12 V / 7 Ah × 16 12 V / 9 Ah × 16 —
Noise at 1 m ≤ 55 dB ≤ 58 dB ≤ 58 dB
Dimensions W × D × H (mm) 191 × 465 × 711 (S)191 × 465 × 350 (H) 191 × 495 × 711 (S)191 × 495 × 350 (H) 191 × 495 × 515 (H)
Net Weight (kg) 53 (S) / 14.5 (H) 62 (S) / 16.5 (H) 26.5 (H)
Gross Weight (kg) 61 (S) / 16 (H) 72 (S) / 18 (H) 28 (H)
Parameter (all models) Specification
Input Wiring Single-phase three-wire (L + N + PE)
Input Rated Voltage 208 / 220 / 230 / 240 VAC
Input Voltage Range 110–176 VAC (linear derating 50–100% load)176–288 VAC (no derating)
Input Frequency 50/60 Hz auto-sensing; range 40–70 Hz
Input Power Factor ≥ 0.99
Bypass Voltage Range -40% to +15% (adjustable)
Input THDi ≤ 5%
Output Wiring Single-phase three-wire (L + N + PE)
Output Rated Voltage 208 V (PF 0.9) / 220 / 230 / 240 VAC
Voltage Regulation ±1%
Output Frequency Synchronized to bypass in mains mode; 50/60 Hz ±0.1% in battery mode
Waveform Pure sine wave
Output Power Factor 0.9
Output THDv ≤ 1% (linear load); ≤ 4% / ≤ 3% (non-linear load)
Overload Capacity 102–110%: 10 min · 110–125%: 1 min · 125–150%: 30 s
Battery DC Voltage 192 VDC (192 / 240 VDC adjustable)
Number of Batteries 16 (16–20 adjustable)
Charging Current Standard: 1 A · Long-run: 5 A default (1–5 A adjustable)
Recharge Time Standard model: 90% in 8 hours · Long-run model: depends on battery capacity
Efficiency ≥ 94% at 100% load; max. 95% at 60% load; ≥ 98% in ECO mode
Transfer Time 0 ms
Protections Short circuit, overload, overtemperature, low battery, overvoltage, undervoltage, fan failure
Parallel Units Up to 4
Communication RS232 (standard); USB, RS485, dry contacts, SNMP, battery temperature compensation (optional)
Display LCD + LED
Operating Temperature 0 °C to +40 °C
Storage Temperature -25 °C to +55 °C (without battery)
Humidity 0–95% (non-condensing)
Altitude ≤ 1000 m; derate 1% per additional 100 m
Protection IP20

Datasheet